IFT Featured Missouri Job 72inch Linestop through a 36inch hottap with 48inch bypasses

Job Status: Successful and Completed
Job Date: Oct 28, 2016
Location: Kansas City, Missouri

Job Specifics:
1 - Hottap 72" x 48'' Pre Stressed Concrete Pipeline (PCCP) with By Pass
1 -72" x 48" Hottap Fitting for PCCP (apx. 40-PSI) (JCM 445 Shop Coated with Epoxy Coated Water Way)
1 -Installation of Hot Tap Fitting (Others to Provide 48" Gate Valve with Installation and Provide Support of Valve)
1 - Pressure Test of Assembly & 48" Hottap
1- 48" Loaner Valve Loaner
48" Knife Gate for Bypass- Removed Under Pressure after By Pass is Terminated. Includes Setting 48" Completion Plug and Supply Blind Flange with Zinc Plated NBG Sets.
1 - 72" Linestop Fitting for PCCP- 72" Inside Diameter (ID) (40 PSI or less) Less than 6 FPS (JCM 445 Shop Coated with Epoxy Coated Water Way)
1- Hot Tap to Allow for Linestop Entry
1 - Insertion of 72" Linestop
1 - 4'' Saddle with Gate Valve and Tap for Blow Down and Equalizing Pressure to Remove Linestops
1- Removal of Linestop, Install Completion Plug and Blind Flange Linestop Held for (7) days.

Linestop® • Valve Inserting • Pipefreeze® • Large Tapping Linestop® is a registered Trademark and Servicemark of International Flow Technologies, Inc.

OR Call

Office hours 7:30 – 5:00 Central time

Nationwide: 1-800-221-3332

Emergency Services Available .

 

 

48" Hottap for a 72" Linestop with a 48" By Pass Video

The City of Kansas City presented IFT with the opportunity to provide our services in order to allow the replacement of 72” valves on a Pre-Stressed Concrete Cylinder Pipe (PCCP) sewage force-main. Their 72” force-main being under pressure was a critical component of the Kansas City sewage collection system and the line could not be shut down.

Continuation of the raw sewage flow was performed by direct pumping from the wet-well into two 48” temporary pipelines that were hot tapped upstream of the 72” Linestop®. The 72” Linestop® plugged sewage from heading toward the wet well infrastructure thus allowing various large diameter valves to be replaced without a shutdown.

This raw sewage was successfully bypassed with use of the IFT Linestop® so the 72” pipeline remained active while the system was upgraded. IFT provides Large Linestop® services on most types of pipelines through 78”. IFT now headed to Houston to perform another 72” Linestop.

Multiple 3/4", 8" and 10" Hottaps, Many 8" and 10" Linestops and a couple 4" Pipe FreezePlug Services

Job Status: Successful and Completed
Job Date: January 28, 2014
Location: Kansas City, MO
Job Specifics: ltem 1 Linestop 6” - Below Computer Floor – Second Floor
8 – 6” Linestop weld fittings for Carbon Steel Chilled Water (Fitting provided by IFT and weld on by Contractor)
8 – Installation of temporary valve with air test.
8 – Hot Taps to allow for linestop entry
8 – Insertion of 6” linestop
8 – 3/4” Tap on contractor supplied and installed materials for blow down and equalizing pressure to remove linestop. (If Needed)
8 – 6” Linestops held up to 8 Hours while you make pipe modifications
8– Removal of Linestop, install Completion Plug and Blind Flange

ltem 2 Linestop 10” - Ceiling of First Floor
4 – 10” Linestop weld fittings for Carbon Steel Chilled Water (Fitting provided by IFT and weld on by Contractor)
4 – Installation of temporary valve with air test.
4 – Hot Taps to allow for linestop entry
4 – Insertion of 10” linestop
4 – 3/4” Tap on contractor supplied and installed materials for blow down and equalizing pressure to remove linestop. (If Needed)
4 – 10” Linestops held up to 8 Hours while you make pipe modifications 4– Removal of Linestop, install Completion Plug and Blind Flange

ITEM 3 – 4” Freeze - Ceiling of First Floor
2 – 4” Pipe freeze on Carbon Steel Chilled Water Pipeline (70 degrees or less ) 6 - Hour hold time for freeze while you perform pipeline modifications

Linestop® • Valve Inserting • Pipefreeze® • Large Tapping Linestop® is a registered Trademark and Servicemark of International Flow Technologies, Inc.

OR Call

Office hours 7:30 – 5:00 Central time

Nationwide: 1-800-221-3332

Emergency Services Available .

 

 

IFT's Missouri Past Work

Missouri Job 7 Dual 30 and 54 inch Linestops

Missouri Job 1 The Van Nuys 48 Inch Wall Taps


Please click your state to view recent jobs. This feature is new to International Flow Technologies and will grow with time. Look below the USA map for a list of complete jobs.

Go to top